09: Battery maximum discharge time setting
Interface
Setting
Parameter 3:
000~999: Set the maximum discharge time from 0min to
999min. UPS will shut down to protect battery after discharge time
arrives. The default value is 990min.
DIS: Disable battery discharge protection and backup time will
depend on battery capacity.
10: reserved
Interface
Setting
reserved
11: reserved
Interface
Setting
reserved
12: reserved
Interface
Setting
reserved
13: Battery voltage calibration
Interface
Setting
Parameter 2: Select Addor Sub function to calibrate battery
voltage to real figure.
Parameter 3: the voltage range is from 0V to 5.7V, the default
value is 0V.